Mains supply 230V 50/60Hz.
Mains rated current 350mA maximum.
Internal power supply 19V-28.5V (27V nominal). Ripple 7V maximum
Total output current limited to 1.5A @ 230Vac (ImaxA eq 146mA)
Quiescent current 25mA (mains failed, internal sounder active, PSU & gen fault LED lit)
Max battery size and type 2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
No. of detector zone circuits 8 (Max. length per circuit is 500m)
Call point resistor value 470 to 680Ω.
Max. devices per detector zone 25 detectors (or 32 detectors/manual call points combined).
No. of conventional sounder circuits 4 (Max. length per circuit is 500m).
EOL resistor value 6800Ω 5% Tol 0/25W (blue, grey, red, gold)
Alarm voltage 27V max, 20V min (final battery voltage)